top of page
OfficePro12-193x300.png
Electronic
Features

Control

Programmable

12,000 Btu/h

Capacity

Rating Conditions: 95°F at 60% H

Electrical 
Characteristics

Voltage Requirement

1 Phase, 115v

Total Power Consumption

Cooling: 1.23 kW, Heating 1.25 kW

Current Consumption

Cooling: 11.1 amps,

Heating: 11.3 amps

Recommended Fuse Size

15 amps

NEMA Plug Configuration

5 – 15P

Min. – Max. Voltage

105 – 125

Fans

Motor Output – high/mid/low

0.14/0.08 kW

Evaporator

Fan Type

Centrifugal

Max. Air Flow – high/mid/low

410/380 CFM

Max. External Static Pressure

0.16 IWG

Compressor

Type

Hermetic Rotary

Output

0.9 kW

Refrigerant

Type

R-410A

Dimensions

W x D X H

21 x 27 x 44 in

Net Weight/
Shipping Weight

196/238 lb

Power Cord

Gauge/Length

12 AWG (3-core)/10 ft

Condensate Tank Capacity

5 gal

Operating Condition

Min. – Max (@ 50% RH)

65° – 95°F

Max. Equivalent Duct Length

Per Cold Duct Hose

30 ft

Hot Duct Hose

60 ft

Max. Sound Level

With Condenser – Duct high/low

52/50 dB(A)

Without Condenser – Duct high/low

55/53 dB(A)

All specification subject to change without notice.