top of page
iStock-179027144_wr.jpg

Climate Pro K36

K36_Left_Shadow.png
Electronic
Features

Control Panel

Programmable

Rating Conditions: 95°F @ 60% RH

36,000 Btu/h

Cooling Capacity

Voltage Requirement

1 Phase, 208-230 V

Electrical 
Characteristics

Total Power Consumption

4.3 kW*

Current Consumption

19.9 amps*

Recommended Fuse Size

30 amps

NEMA Plug Configuration

6-30P

Min. – Max. Voltage

198 – 253 V

Fans

Motor Output @ 230V

0.23 kW Evaporator

0.37 kW Condenser

Fan Type

Centrifugal

Evaporator

Max. Air Flow – High/Mid/Low

920/880/840 CFM

Max. External Static Pressure

0.6 IWG

Fan Type

Centrifugal

Condensor

Max. Air Flow – High/Mid/Low

1390/990 CFM

Max. External Static Pressure

0.5 IWG

Compressor

Type

Hermetic Rotary

Output

2.3 kW

Refrigerant

Type

R-410A

Dimensions

W x D X H

31 x 55 x 53 in

Net Weight/
Shipping Weight

454  / 535 lb

Power Cord

Gauge

12 AWG (3-core)

Length

6 ft

Condensate Tank Capacity

2 @ 5 gal

Operating Condition

Min. – Max (@ 50% RH)

65°F – 95°F

Max. Duct Length

Per Cold Duct Hose

40 ft

Exhaust Duct Hose

60 ft

Max. Sound Level

With Condenser Duct – High/Mid /Low

68/67/66 dB(A)

Without Condenser Duct – High/ Mid/Low

70/69/68 dB(A)

*Specification information shown with 230V

All specification subject to change without notice.