top of page
classic-plus-14-195x300 (1).png
Electronic
Features

Control

Programmable

Cooling Capacity

 13,200 Btu/h

Rating Conditions: 95°F at 60% RH

Electrical 
Characteristics

Voltage Requirement

1 Phase, 1150v

Total Power Consumption

1.3 kW

Current Consumption

11.9 amps

Recommended Fuse Size

15 amps

NEMA Plug Configuration

5 – 15

Min. – Max. Voltage

105 – 125

Fans

Motor Output – high/mid

0.24/0.19 kW

Evaporator

Fan Type

Centrifugal

Max. Air Flow – high/mid/low

440/380 CFM

Max. External Static Pressure

0.31 IWG

Fan Type

Max. Air Flow – high/mid/low

880/760 CFM

Max. External Static Pressure

0.19 IWG

Condenser

Centrifugal

Compressor

Type

 Hermetic Scroll

Output

 0.9 kW

Refrigerant

Type

R-410A

Dimensions

W x D X H

19 x 26 x 31 in

166/197 lb

Net Weight/
Shipping Weight
Power Cord

Gauge/Length

14 AWG (3-core)/6 ft

Condensate Tank Capacity

5 gal

Operating Condition

Min. – Max (@ 50% RH)

70° – 113°F

Hot Duct Hose

60 ft

Max. Equivalent Duct Length

Per Cold Duct Hose

30 ft

Max. Sound Level

With Condenser – Duct high/low

57/55 dB(A)

Without Condenser – Duct high/low

60/58 dB(A)

All specification subject to change without notice.