CMW30

CMW30
Electronic Features Operation
Control
Wall Mounted Controller
Programmable
Electrical Characteristics Voltage Requirements 1 Phase, 208/230V
Recommended Fuse Size 20 amps
Min. – Max. Voltage 198 – 250
Cooling Capacity and Power Consumption
Evaporator: 80°F, 50% RH
Condenser: EWT/LWT: 85°F/95°F
Total Cooling Capacity  29,400 Btu/h1
Sensible Cooling Capacity 20,800 Btu/h1
Power Consumption 1.99 kW1
Current Consumption 8.9 amps1
Evaporator: 72°F, 50% RH
Condenser: EWT/LWT: 85°F/95°F
Total Cooling Capacity  25,200 Btu/h1
Sensible Cooling Capacity 22,000 Btu/h1
Power Consumption 2.00 kW1
Current Consumption 9 amps1
IEER 17.0
Evaporator Fan Type Centrifugal1
Max. Air Flow – high/low 1060/840 CFM
Max. External Static Pressure 0.66 IWG
Compressor Type Hermetic Swing Inverter
Refrigerant Type R-410A
Dimensions W x D x H (without flange) 45 x 32 x 20 in
W x D x H (with flange) 49 x 35 x 20 in
Net Weight/Shipping Weight 236/271 lb
Condensate Tank Capacity Pump Rate 5 gal/h
Head  4 ft
Operating Conditions Evaporator 55°F – 95°F, 50% RH
Condenser  45°F – 115°F (Condenser Water)
MaximumDuct Length Cold Duct Hose 120 ft2
Hot Duct Hose N/A
Maximum Sound Level Under Ceiling Title with Evaporator Duct 55 dB(A)

Outstanding Reputation,
Quality Equipment,
Dependable Service

Protect Your Project or Facility

Contact us today for a free quote, and learn how affordable it can be to rent or buy the temporary climate solution your company needs.